GEYA GRD9L-R-AC220V+A-SI RCCB 2P-63A-30mA

GEYA GRD9L-R Otomatik Yeniden Kapatma Cihazı Kullanım Kılavuzu

Model: GRD9L-R-AC220V+A-SI RCCB 2P-63A-30mA

1. Ürün Bittiview

The GEYA GRD9L-R Automatic Reclosing Device is an electromagnetic leakage circuit breaker (RCCB) designed to enhance electrical system reliability and reduce manual intervention. It automatically recloses the circuit when a leakage fault causes the RCD to trip unexpectedly, minimizing downtime and maintenance costs.

This device is suitable for various applications, including electrical network terminal lines, meter boxes, new energy circuit management, solar PV control boxes, smart electricity systems, smart homes, and charging stations for new energy vehicles.

Temel Özellikler:

  • Automatic reclosing function after RCD trip, eliminating the need for manual reset.
  • Integrated 3 reclosing attempts. An auxiliary contact can send an alarm if continuous tripping occurs within 15 minutes.
  • Manual/Automatic selector switch for operational flexibility.
  • Features double mechanical/electronic locking for enhanced safety.
  • Compatible with auxiliary contacts, alarm contacts, shunt releases, and undervoltage releases.
  • Reclosing attempt counter resets if no trip occurs or after a manual reset within 15 minutes of successful reclosure.
GEYA GRD9L-R Automatic Reclosing Device

Şekil 1: Ön view of the GEYA GRD9L-R Automatic Reclosing Device.

2. Güvenlik Bilgileri

UYARI: Installation and maintenance of this device must be performed by a qualified electrician in accordance with all local and national electrical codes and regulations. Failure to do so may result in electric shock, fire, or other serious injury.

  • Cihazı takmadan, bakımını yapmadan veya çıkarmadan önce daima güç bağlantısını kesin.
  • Elektrik sisteminin doğru şekilde topraklanmasını sağlayın.
  • Cihazın hasarlı olduğu görülüyorsa cihazı çalıştırmayın.
  • Verify correct wiring connections to prevent malfunction or damage.
  • The device is designed for specific voltage and current ratings. Do not exceed these limits.

3. Product Components and Diagrams

3.1 İşlev Açıklaması

Function Description Diagram

Figure 2: Diagram illustrating the automatic reclosing logic and function description. The device attempts to reclose the circuit up to three times with specific time intervals. If the interval between two successful closings exceeds 15 minutes, the program clears the accumulated closing times.

3.2 Functions Diagram (Auto Mode Logic)

Functions Diagram Auto Mode

Figure 3: Detailed flow chart of the automatic reclosing sequence. After a trip, the device attempts to reclose. If successful, it waits. If it trips again, it attempts a second reclose after 10 seconds. A third attempt follows after 60 seconds if the second fails. If all three attempts fail within 15 minutes, the device locks out and sends an auxiliary alarm. The power delay (Tr) is 2 seconds. Note: Customization of closing times and delay times requires contacting the manufacturer.

3.3 Kilitleme Fonksiyonu

Locking Function Diagram

Figure 4: Illustration of the locking mechanism. When the locking function is activated (e.g., by inserting a padlock with a diameter less than 3.5 mm), the RCCB cannot be closed, ensuring safety during circuit checks or maintenance. This prevents accidental reclosure.

4. Kurulum ve Kurulum

The GEYA GRD9L-R device is designed for DIN rail mounting and can be integrated with other electrical components such as an RCCB and auxiliary modules.

4.1 Component Integration

Component Integration Diagram

Şekil 5: Ör.ample of how the GRD9L-R device can be installed alongside an Auxiliary module and an RCCB on a standard DIN rail. Ensure proper alignment and secure fastening of all components.

4.2 Kablolama Şeması

Bağlantı Şeması Örn.ample

Şekil 6: Eski sevgiliample application wiring diagram. This diagram shows the connection of the GRD9L-R device with an alarm lamp, an RCCB, and multiple load circuits. Red lines indicate live connections, blue lines indicate neutral connections. The auxiliary contacts (A1, A2, COM, NO) are used for external signaling, such as an alarm lamp. Always consult a qualified electrician for correct wiring specific to your installation.

4.3 Installation Steps (General Guidelines):

  1. Güç Bağlantısının Kesilmesi: Kurulum işlemine başlamadan önce devrenin ana güç kaynağının tamamen bağlantısının kesildiğinden emin olun.
  2. Montaj: Mount the GRD9L-R device, the associated RCCB, and any auxiliary modules onto a standard DIN rail within an appropriate electrical enclosure.
  3. Kablolama: Connect the input and output terminals of the GRD9L-R and RCCB according to the wiring diagram (Figure 6) and local electrical codes. Pay close attention to live (L) and neutral (N) connections.
  4. Yardımcı Bağlantılar: If using, connect auxiliary contacts (A1, A2, COM, NO) for remote signaling or control, such as an alarm lamp.
  5. Doğrulama: Tüm kablo bağlantılarının sıkılığını ve doğruluğunu iki kez kontrol edin.
  6. Güç Restorasyonu: Kurulum tamamlanıp doğrulandıktan sonra devreye tekrar güç verin.

5. Kullanım Talimatları

5.1 Manual/Automatic Selector

The device features a selector switch labeled "AUTO" and "MANU" (Manual). This switch allows you to choose the operating mode:

  • Otomatik mod: In this mode, the device will automatically attempt to reclose the associated RCCB after a trip, following the reclosing logic described in Figure 3. This is the default and recommended mode for continuous operation.
  • MANU Mode: In this mode, the automatic reclosing function is disabled. If the RCCB trips, it must be manually reset. This mode is useful for maintenance or specific operational requirements where automatic reclosure is not desired.

5.2 Reclosing Logic (Auto Mode)

When in AUTO mode, the device follows a specific sequence of reclosing attempts:

  1. 1st Trip: If the RCD trips, the device waits for 10 seconds, then attempts to reclose.
  2. 2nd Trip: If the RCD trips again within 15 minutes of the first reclosure, the device waits for 60 seconds, then attempts a second reclosure.
  3. 3rd Trip: If the RCD trips a third time within 15 minutes of the second reclosure, the device waits for 300 seconds (5 minutes), then attempts a third reclosure.
  4. Kilitleme: If the RCD trips a fourth time within 15 minutes, or if any of the three reclosing attempts fail, the device enters a lockout state. It will not attempt further reclosures automatically and will activate the auxiliary alarm contact (if connected). Manual intervention is required to reset the device.
  5. Resetting Closing Times: If no trip occurs for 15 minutes after a successful reclosure, or if the device is manually reset, the reclosing attempt counter is cleared.

5.3 Test Düğmesi

The associated RCCB typically has a test button. Pressing this button simulates a leakage fault and should cause the RCCB to trip. This is used to verify the proper functioning of the RCCB and, in AUTO mode, the reclosing device.

6. Bakım

The GEYA GRD9L-R Automatic Reclosing Device is designed for minimal maintenance. However, regular checks are recommended to ensure optimal performance and safety.

  • Görsel Muayene: Cihazı periyodik olarak fiziksel hasar, renk değişimi veya gevşek bağlantı belirtileri açısından kontrol edin.
  • İşlevsellik Testi: Regularly test the associated RCCB using its test button. Observe if the GRD9L-R device initiates its reclosing sequence in AUTO mode.
  • Temizlik: Ensure the device is kept clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquid cleaners.
  • Profesyonel Muayene: It is recommended to have the electrical system, including this device, inspected by a qualified electrician at least once a year.

7. Sorun Giderme

If the GEYA GRD9L-R device is not functioning as expected, consider the following:

SorunOlası NedenÇözüm
Cihaz otomatik olarak yeniden kapanmıyor.
  • Device is in MANU mode.
  • Device is in lockout state after multiple failed reclosures.
  • Persistent fault in the circuit.
  • Locking function is activated.
  • Switch to AUTO mode.
  • Manually reset the device and investigate the cause of repeated trips.
  • Identify and rectify the electrical fault.
  • Ensure no padlock is inserted in the locking mechanism.
Alarm contact is continuously active.
  • Device is in lockout state.
  • Auxiliary contact wiring issue.
  • Investigate and clear the fault, then manually reset the device.
  • Check wiring of auxiliary contacts.
RCCB trips immediately after reclosure.
  • Persistent or severe electrical fault (e.g., short circuit, ground fault).
  • Immediately disconnect power and have a qualified electrician diagnose and repair the fault. Do not attempt further reclosures until the fault is resolved.

If the problem persists after attempting these solutions, contact a qualified electrician or GEYA customer support.

8. Özellikler

ÖzellikDetay
Model NumarasıGRD9L-R-AC220V+A-SI RCCB 2P-63A-30mA
MarkaGEYYA
Cilttage220 Volt AC
Anma Akımı63 A (as per model number)
Kutup sayısı2
Devre Kesici TipiRCD (Kaçak Akım Cihazı)
Montaj TipiWall Mount, Flush Mount (DIN Rail compatible)
Paket Boyutları12x11.6x9.1 cm
Ürün Ağırlığı350 gram
ÜreticiZHEJIANG GEYA ELECTRICAL CO.,LTD

9. Garanti ve Destek

Specific warranty information for the GEYA GRD9L-R Automatic Reclosing Device is not available in the provided product details. Please refer to the product packaging or contact GEYA customer support for detailed warranty terms and conditions.

For technical support, inquiries, or assistance with installation and troubleshooting, please contact GEYA directly through their official channels or the retailer from whom the product was purchased.

İlgili Belgeler - GRD9L-R-AC220V+A-SI RCCB 2P-63A-30mA

Önview GEYA Elektrik Ekipmanları Kataloğu - Devre Kesiciler, Kontaktörler ve Daha Fazlası
Minyatür devre kesiciler, kontaktörler, transfer anahtarları ve diğer güvenlik ekipmanları dahil olmak üzere GEYA elektrik ürünlerinin kapsamlı kataloğu, teknik özellikleri, uygulamaları ve uyumluluk standartlarını ayrıntılı olarak açıklamaktadır.
Önview GEYA GRD9L-W WiFi Kontrollü MCB/RCCB/RCBO: Kullanım Kılavuzu ve Teknik Rehber
GEYA GRD9L-W WiFi kontrollü MCB/RCCB/RCBO için kapsamlı kullanım kılavuzu ve teknik rehber. Akıllı elektrik sistemleri için uygulamaları, özellikleri, teknik özelliklerini, kurulumunu, ağ bağlantısını, sorun gidermeyi ve boyut detaylarını kapsar.
Önview GEYA GRD9L-W WiFi Kontrollü MCB/RCCB/RCBO: Kullanım Kılavuzu ve Teknik Rehber
Detailed instruction manual for the GEYA GRD9L-W WiFi-controlled MCB/RCCB/RCBO. Covers applications in intelligent household electricity management and photovoltaic systems, function features, technical parameters, panel and wiring diagrams, installation, networking setup with Tuya Smart app, common faults, and dimensions. Essential guide for safe and efficient electrical control.
Önview GEYA Miniature Circuit Breakers, Contactors, and Transfer Switches Catalog | Technical Specifications
Comprehensive catalog from GEYA detailing Miniature Circuit Breakers (MCB), Residual Current Circuit Breakers (RCCB), Residual Current Circuit Breakers with Overcurrent Protection (RCBO), Molded Case Circuit Breakers (MCCB), AC Contactors, Automatic Transfer Switches, and Intelligent Circuit Breakers. Includes technical specifications, scope of application, product features, and compliance information for various models, serving industrial, commercial, and residential applications.
Önview GEYA WiFi Serisi Akıllı Minyatür Devre Kesici - Kullanım Talimatları
GEYA WiFi Serisi Akıllı Minyatür Devre Kesici (ZJSB9 serisi) için ayrıntılı kullanım talimatları ve SSS. Akıllı ev elektrik koruması için kurulum, ayar, sorun giderme, güvenlik ve uygulama hakkında bilgi edinin.
Önview GEYA GPS8-10 Voltage/Current Protector Instruction Manual
Instruction manual for the GEYA GPS8-10 Voltage/Current Protector, detailing its applications, features, technical parameters, wiring, panel diagram, parameter settings, factory settings, and functional diagrams.