1. Giriş
The SINOTIMER STVP series automatic over-voltage ve alt hacimtage protector is designed for three-phase 3*127V/220VAC power systems with a rated working current of 80A. This device provides essential protection for electrical equipment by instantaneously cutting off the power supply when over-voltage, cilt altıtage, or over-current conditions are detected. Once the circuit voltage returns to normal, the protector automatically restores power, ensuring continuous operation and safeguarding your appliances from damage.
This protector integrates multiple protection functions including over-voltage, cilt altıtage, over-current, three-phase current (voltage) imbalance, phase sequence (reverse phase), zero-break, and phase-break protection. It also features voltmeter and ammeter functions, and the ability to restore factory settings. The device offers comprehensive features, stable performance, and ease of operation.
Ayrıntılı kullanıcı kılavuzunu PDF formatında indirebilirsiniz: Kullanım Kılavuzu (PDF)
2. Temel Özellikler
- aşırı sestage koruma
- hacim altıtage koruma
- Aşırı akım koruması
- Otomatik kurtarma
- Cilttage display (separate ABC phase voltage ölçümü)
- Ampere display (separate ABC phase ampere measurement)
- Üç fazlı ampere unbalance protection
- Phase sequence protection (reverse phase protection)
- Zero line break protection
- Faz hatası koruması
- Fault inquiry function
- Rotation display of voltage and current for each phase
- Adjustable over-voltage protection value and recovery value
- Adjustable under-voltage protection value and recovery value
- Adjustable over-current protection value and action time
- Adjustable 3-phase ampere unbalance protection value and action time
- Adjustable delay time after power-on
- Adjustable fault recovery delay time
- Factory data reset function
3. Ürün Özellikleri
| Bağlanmak | Değer |
|---|---|
| Model Numarası | STVP936-1-80A |
| Güç Kaynağı | 3*127V/220VAC 60Hz |
| Anma Hacmitage | 220V |
| Faz | Üç fazlı |
| Maks. Alan sayısı Yük Akımı | 1~80A Adjustable (default: 80A) |
| aşırı sestage Koruma Aralığı | 121V-150V-OFF Adjustable (default: 140V) |
| aşırı sestage Recovery Range | 120V-149V (default: 135V) |
| aşırı sestage Action Time | 0.1~10 seconds (default: 0.2s) |
| hacim altıtage Koruma Aralığı | 118V-80V-OFF Adjustable (default: 90V) |
| hacim altıtage Recovery Range | 118V-91V (default: 95V) |
| hacim altıtage Action Time | 0.1~10 seconds (default: 0.2s) |
| 3-Phase Volt Unbalance Protection | 10%~50%~OFF (default: 20%) |
| 3-Phase Volt Unbalance Action Time | 0.1~10 seconds (default: 1s) |
| Delay Time After Power-on | 2~255 seconds (default: 2s) |
| Fault Recovery Delay Time | 2~600 seconds (default: 60s) |
| Ekran Modeli | LCD |
| Boyutlar | 71.5mm (W) * 95.2mm (H) * 65.7mm (D) |
| Kurulum | 35mm DIN Ray |
| Sertifikasyon | CE, RoHS |
4. Güvenlik Bilgileri
- Kurulum ve bakım sadece kalifiye elektrikçiler tarafından yapılmalıdır.
- Herhangi bir montaj veya kablolama işlemine başlamadan önce güç kaynağının bağlantısının kesildiğinden emin olun.
- The device does not provide overload or short-circuit protection. It must be used in conjunction with appropriate external circuit breakers (e.g., C45, C65 mini circuit breakers) for comprehensive protection.
- Gücü vermeden önce tüm kablo bağlantılarının sağlam ve doğru olduğundan emin olun.
- Do not operate the device in wet or hazardous environments.
5. Kurulum
5.1 Fiziksel Boyutlar

5.2 Montaj
The protector is designed for 35mm DIN rail installation. Snap the device onto the DIN rail securely.

5.3 Kablolama Şeması
Connect the input and output terminals as shown in the diagram below. Ensure correct phase (L1, L2, L3) and neutral (N) connections. The input terminals are located at the top, and output terminals at the bottom.


6. Kurulum ve Yapılandırma
Ayar moduna girmek için, tuşuna basın ve basılı tutun. AYARLAMAK button for 3 seconds. Then, continuously press AYARLAMAK to cycle through the parameters. Use the ▲ Ve ▼ buttons to adjust the values. When "ENd" appears, press AYARLAMAK again to save the data and exit the setting mode.
If no operation is performed within 10 seconds after pressing AYARLAMAK, the device will automatically exit the setting mode, and any unsaved changes will be lost.
6.1 Parameter Settings Table
| Adım | İçerik | LCD Ekran | Description / Range (Default) |
|---|---|---|---|
| 1 | aşırı sestage koruma değeri | Uvo 280V | 221V-300V-OFF (280V) |
| 2 | aşırı sestage kurtarma değeri | Uvor 250V | 220V-299V (250V) |
| 3 | aşırı sestage koruma eylem süresi | 0.2'lar | 0.1-10sn (0.2sn) |
| 4 | hacim altıtage koruma değeri | Uve 160V | 219V-150V-OFF (160V) |
| 5 | hacim altıtage kurtarma değeri | Uver 180V | 151V-220V (180V) |
| 6 | hacim altıtage koruma eylem süresi | 0.2'lar | 0.1-10sn (0.2sn) |
| 7 | Aşırı akım koruma değeri | >In 80A | 1-80A (80A) |
| 8 | Over-current protection action time | 5S | 1-512sn (5sn) |
| 9 | 3 faz amp unbalance protection value | >In % | 5%-90%-OFF (25%). Not active if current < 2A. |
| 10 | 3 faz amp unbalance protection action time | 1.0 S | 0.1-10sn (1sn) |
| 11 | Faz sırası koruması | ON ABC | ON or OFF (ON) |
| 12 | Güç açma gecikme süresi | 2 S | 2-255sn (2sn) |
| 13 | Fault recovery delay time | 60 S | 2-512sn (60sn) |
| 14 | Fault inquiry code | E0 | Press ▲ to view last 5 fault records (E1-E5). >U for overvoltage, <U for undervoltage. |
| 15 | Bitiş | Son | Press SET to save and exit. |
6.2 Fabrika Ayarlarına Sıfırlama
To reset the device to factory settings, press and hold the ▲ Ve ▼ düğmelerine aynı anda 3 saniye boyunca basın.
7. Operasyon
Once installed and configured, the device will continuously monitor the three-phase power supply. The LCD screen will automatically rotate to display the real-time voltage and current for each phase (L1, L2, L3).
Aşırı ses durumundatage, cilt altıtage, or over-current event, the protector will automatically trip and cut off the power supply to protect connected equipment. After the fault condition clears and the recovery delay time has passed, the device will automatically restore power.
8. Sorun Giderme
8.1 Fault Inquiry
If a fault occurs, the device will display an error code (E0). You can press the ▲ button to query the last 5 fault records (E1-E5). The display will indicate:
- ">U" for overvoltage olaylar.
- "<U" for undervoltage olaylar.
8.2 Phase Sequence Error
If the LCD displays "ABC" character, it indicates a phase sequence error. To correct this, arbitrarily reverse any two of the three phase lines (L1, L2, L3) at the input.
9. Bakım
- Cihazınızı temiz tutun, toz ve nemden uzak tutun.
- Kablo bağlantılarının sıkılığını ve aşınma veya hasar belirtilerini düzenli olarak kontrol edin.
- Do not attempt to repair the device yourself. Refer to qualified personnel for service.
10. Garanti ve Destek
For technical support, inquiries, or warranty claims, please contact the distributor:
Dağıtıcı: XNY INTERNATIONAL LIMITED
Adres: Room 20A, Kiu Fu Commercial Building, 300 Lockhart Road, Wanchai, Hong Kong.
Telefon: 0086 57761733853
Faks: 0086 577 89736991
WhatsApp: 0086 1565857 3377
Wechat: sinotimer
Skype: sinotimer
Web: www.sinotimer.com
E-posta: info@sinotimer.com