NJTy T-6125

NJTy T-6125 Digital Isolation Tester User Manual

Modeli: T-6125

1. Giriş

Thank you for choosing the NJTy T-6125 Digital Isolation Tester. This device is a professional-grade instrument designed for accurate measurement of insulation resistance, absorption ratio, polarization index, AC voltage, and low resistance. It features a high-performance integrated circuit, wide measurement range, and multiple test voltage levels, making it an essential tool for electricians and maintenance technicians. This manual provides detailed instructions for safe and effective operation, maintenance, and troubleshooting.

NJTy T-6125 Digital Isolation Tester front view

Şekil 1: Ön view of the NJTy T-6125 Digital Isolation Tester, showing the large LCD display and control dial.

2. Güvenlik Bilgileri

Please read and understand all safety warnings and operating instructions before using this instrument. Failure to follow these instructions may result in electric shock, fire, or serious injury.

  • Kullanmadan önce cihazın iyi çalışır durumda olduğundan emin olun. Hasarlıysa kullanmayın.
  • Do not operate the tester in wet environments or explosive atmospheres.
  • Wear appropriate personal protective equipment (PPE), such as insulated gloves and safety glasses, when performing electrical measurements.
  • Verify that the circuit under test is de-energized before connecting or disconnecting test leads, unless performing live voltage measurements as specified.
  • Voltaj için maksimum giriş değerlerini aşmayın.tage ve akım.
  • Çalıştırmadan önce pil bölmesinin güvenli bir şekilde kapatıldığından emin olun.
  • Refer to the warning label on the back of the device: "TO AVOID ELECTRICAL SHOCK, REMOVE TEST LEADS BEFORE OPENING CASE. READ OPERATING MANUAL."

3. Ürün Bittiview

3.1 Temel Özellikler

  • Çok Yönlü Ölçüm: Measures insulation resistance, absorption ratio (DAR), polarization index (PI), AC voltage, and low resistance.
  • Yüksek Performans: Professional-grade integrated circuit design with wide measurement range and high output power.
  • Multiple Test VoltagTürkçe: Offers 100V, 250V, 500V, 1000V, and 2500V test voltage options for insulation resistance.
  • Kullanıcı Dostu Ekran: Large LCD screen with grey-white backlight for easy readability.
  • Veri Yönetimi: Features measurement data retention (HOLD), excessive alarm, and automatic shutdown.
  • Dayanıklı Yapı: Designed to be shock-resistant and dust-proof, suitable for various electrical equipment testing.
  • Automatic Discharge: Includes an automatic discharge function after insulation resistance testing.

3.2 Bileşenler ve Aksesuarlar

NJTy T-6125 Digital Isolation Tester with included accessories

Figure 2: The NJTy T-6125 Isolation Tester shown with its carrying case, test leads, and alligator clips.

Paket genellikle şunları içerir:

  • NJTy T-6125 Digital Isolation Tester
  • Test Leads (Red, Black, Green)
  • Timsah klipsleri
  • Taşıma Çantası
  • Kullanım Kılavuzu (bu belge)
Close-up of NJTy T-6125 display and anti-fall plastic shell

Figure 3: Detail showing the large backlit LCD display and the robust, anti-fall plastic shell design of the T-6125.

4. Kurulum

4.1 Pil Kurulumu

  1. Ensure the device is powered off and all test leads are disconnected.
  2. Test cihazının arka tarafında bulunan pil bölmesi kapağını bulun.
  3. Pil bölmesi kapağını açmak için tornavida kullanın.
  4. Insert 8 x 1.5V AA batteries, observing the correct polarity (+/-) as indicated inside the compartment.
  5. Securely close the battery compartment cover and fasten the screws.
Geri view of NJTy T-6125 showing battery compartment

Şekil 4: Arka view of the T-6125, highlighting the battery compartment cover.

Open battery compartment of NJTy T-6125

Figure 5: The open battery compartment, showing the slots for 8 AA batteries.

4.2 Test Uçlarının Bağlanması

Connect the test leads to the appropriate input terminals on the tester. Ensure a secure connection before proceeding with any measurements.

5. Kullanım Talimatları

5.1 Açma/Kapatma

  • To power on, rotate the central rotary switch from the "OFF" position to the desired measurement function.
  • To power off, rotate the central rotary switch to the "OFF" position.
  • The device features an automatic shutdown function after 30 minutes of inactivity to conserve battery life.
NJTy T-6125 showing 30 minutes automatic shutdown feature

Figure 6: Illustration of the 30-minute automatic shutdown feature for battery conservation.

5.2 Yalıtım Direnci Ölçümü

  1. Test edilecek devrenin enerjisinin kesildiğinden ve güvenli bir şekilde deşarj edildiğinden emin olun.
  2. Connect the test leads to the circuit or component to be tested.
  3. Rotate the central switch to one of the insulation resistance test voltage settings (e.g., 250V, 500V, 1000V, 2500V).
  4. Basın TEST Ölçümü başlatmak için düğmeye basın. Ekranda yalıtım direnci değeri görüntülenecektir.
  5. After the test, the device will automatically discharge the circuit.
  6. Basın TUTMAK button to retain the displayed measurement. Press again to release.

5.3 Absorption Ratio (DAR) and Polarization Index (PI) Measurement

  1. Follow steps 1-3 for insulation resistance measurement.
  2. Rotate the central switch to the "DAR/PI" position.
  3. Basın TEST button. The device will perform timed insulation resistance measurements to calculate DAR and PI.
  4. The results will be displayed sequentially.

5.4 AC Hacmitage Ölçüm

  1. Test uçlarını AC voltajına bağlayıntage kaynak.
  2. Rotate the central switch to the "ACV" position.
  3. AC cilttage ekranda görüntülenecektir.

5.5 Low Resistance Measurement

  1. Test edilen devrenin enerjisinin kesildiğinden emin olun.
  2. Connect the test leads to the component for low resistance measurement.
  3. Rotate the central switch to the "Low Resistance" position (indicated by Ω).
  4. The resistance value will be displayed.
NJTy T-6125 in various application scenarios

Figure 7: The T-6125 being used in diverse applications such as industrial control panels, telecommunication towers, circuit boards, and automotive electrical systems.

6. Bakım

  • Temizlik: Yumuşak bir d kullanınamp Cihazın dış yüzeyini temizlemek için bir bez kullanın. Aşındırıcı temizleyiciler veya çözücüler kullanmayın.
  • Pil Değişimi: Replace batteries promptly when the low battery indicator appears. Always use new, identical batteries.
  • Depolamak: Uzun süre kullanılmadığında sızıntıyı önlemek için pilleri çıkarın. Cihazı serin, kuru bir yerde, doğrudan güneş ışığından ve aşırı sıcaklıklardan uzakta saklayın.
  • Kalibrasyon: Profesyonel kullanımlarda doğruluğun sağlanması için kalifiye personel tarafından periyodik kalibrasyon yapılması önerilir.

7. Sorun Giderme

SorunOlası NedenÇözüm
Cihaz açılmıyor.Piller bitmiş veya yanlış takılmış.Check battery polarity and replace with new batteries if necessary.
Hatalı okumalar.Poor test lead connection, dirty terminals, or device needs calibration.Ensure test leads are securely connected. Clean terminals. Consider professional calibration.
Ekran soluk veya titriyor.Pil gücü düşük.Tüm pilleri değiştirin.
Cihaz beklenmedik şekilde kapanıyor.Automatic shutdown due to inactivity, or low battery.This is a normal feature after 30 minutes of inactivity. If it happens during active use, replace batteries.

8. Özellikler

ParametreDeğer
ÖrnekT-6125
MalzemeABS
Insulation Test Measurement Range0.01MΩ ~ 200.0 GΩ
Yalıtım Testi Hacmitages100V, 250V, 500V, 1000V, 2500V
Insulation Test Output Voltage Doğruluk±%10
Insulation Test Short-Circuit CurrentYaklaşık 2 mA
Otomatik Boşaltma FonksiyonuEvet
Depolama Sıcaklığı-20 ℃ ~ 60 ℃
Çalışma Koşulları Sıcaklık0 ℃ ~ 40 ℃
Yükseklik2000m
Bağıl nem%40 ~ %75
Güç Kaynağı8 adet 1.5V AA pil (dahil değildir)
Paket Boyutları22x19x9 cm
Ağırlık923 gram
ÜreticiEVTSCAN
Menşei ülkeÇin

9. Garanti ve Destek

For warranty information and technical support, please refer to the documentation provided at the time of purchase or contact your retailer. Specific warranty terms may vary by region and seller.

© 2023 NJTy. All rights reserved.