RWRAPS TOQ5-63, TOQ5-100, TOQ5-125

RWRAPS Din Rail ATS Dual Power Automatic Transfer Switch User Manual

Models: TOQ5-63, TOQ5-100, TOQ5-125 (2P, 3P, 4P variants)

1. Giriş

This manual provides essential information for the safe and effective installation, operation, and maintenance of your RWRAPS Din Rail ATS Dual Power Automatic Transfer Switch. Please read this manual thoroughly before installation and operation to ensure proper functionality and safety.

The RWRAPS ATS is designed to automatically switch between two power sources, typically city power and a generator, ensuring an uninterrupted power supply to your load. It is a PC-level switch with a transfer time of less than 8ms, preventing power interruptions during transitions.

Important Note: This device is designed for use with city power and generator systems only. It is not suitable for photovoltaic (PV) systems or inverters.

2. Güvenlik Bilgileri

  • Installation and maintenance must be performed by qualified electricians only.
  • Ensure all power sources are disconnected before installation or servicing to prevent electric shock.
  • Verify correct wiring and connections according to local electrical codes and this manual.
  • Hasarlı görünüyorsa şalteri çalıştırmayın.
  • The device contains live parts; avoid contact during operation.
  • Bağlı tüm ekipmanların uygun topraklamasının yapıldığından emin olun.

3. Ürün Bittiview ve Özellikler

The RWRAPS ATS is designed for reliable automatic transfer between main and backup power sources. Key features include:

  • Otomatik çalışma: Seamlessly switches power sources without manual intervention.
  • Rapid Transfer: Ensures power continuity with a transfer time of less than 8 milliseconds.
  • High Conductivity: Utilizes silver contacts for enhanced conductivity and extended product lifespan.
  • Signal Output Port: Built-in port for connecting signal indicator lights, allowing for convenient status observation.
  • Dayanıklı Yapı: Features good insulation, high temperature resistance, and anti-aging properties for reliable and safe operation.
  • DIN Ray Montajı: Standart DIN raylarına kolay montaj için tasarlanmıştır.

Ürün Views

RWRAPS ATS Dual Power Automatic Transfer Switch, showing various pole configurations (2P, 3P, 4P) and current ratings (63A, 100A, 125A).
Şekil 3.1: Üzeriview of RWRAPS ATS models, illustrating different pole configurations and current ratings. This image shows the general design and labeling for various versions of the automatic transfer switch.
Close-up of RWRAPS 2-Pole 100A ATS, showing 'Source A' and 'Source B' terminals, manual/auto switch, and indicator lights.
Şekil 3.2: Ayrıntılı view of a 2-Pole, 100A RWRAPS ATS. This image highlights the input terminals for Source A (City Power) and Source B (Generator), the manual/automatic selector switch, and the status indicator lights.
Close-up of RWRAPS 3-Pole 125A ATS, showing 'Source A' and 'Source B' terminals, manual/auto switch, and indicator lights.
Şekil 3.3: Ayrıntılı view of a 3-Pole, 125A RWRAPS ATS. This image shows the three-phase input terminals for Source A and Source B, along with the control interface and indicators.
Close-up of RWRAPS 4-Pole 100A ATS, showing 'Source A' and 'Source B' terminals, manual/auto switch, and indicator lights.
Şekil 3.4: Ayrıntılı view of a 4-Pole, 100A RWRAPS ATS. This image displays the four-phase input terminals for both power sources, the manual/automatic selector, and the status indicators.
Taraf view of RWRAPS 2-Pole 100A ATS, showing load side terminals and DIN rail mounting clip.
Şekil 3.5: Yan view of a 2-Pole, 100A RWRAPS ATS, illustrating the load side terminals and the integrated DIN rail mounting mechanism at the bottom.

4. Özellikler

ParametreDeğer
MarkaRWRAPS
Model SerisiTOQ5 (63A, 100A, 125A variants)
Pole Configurations2P, 3P, 4P
Çalışma ModuOtomatik
Transfer SüresiLess than 8ms (PC Level)
Anma Çalışma Akımı63A, 100A, 125A (depending on model)
Anma Çalışma Hacmitage220V AC (2P), 400V AC (3P, 4P)
Yalıtım Hacmitage690V AC
Impact-Resistant Voltage8 kV
Tse ClassPC
Sıklık50/60Hz
StandartIEC / EN60947-6-1
Montaj TipiDIN Ray
İletişim MalzemesiGümüş
Ürün AğırlığıApproximately 2.2 pounds (varies by model)

5. Kurulum ve Kurulum

Başlamadan Önce: Ensure all power is disconnected from both the main utility and the generator. Use appropriate personal protective equipment (PPE).

  1. Montaj: Securely mount the RWRAPS ATS onto a standard DIN rail within an electrical enclosure. Ensure adequate ventilation and clearance around the device.
  2. Wiring Main Power (Source A):
    • Connect the main utility power (City Power) to the "Source A" terminals on the ATS.
    • Ensure correct phase sequence (L1, L2, L3 for 3P/4P models) and neutral connection (N for 2P/4P models).
  3. Wiring Backup Power (Source B):
    • Connect the generator power to the "Source B" terminals on the ATS.
    • Maintain consistent phase sequence and neutral connection with Source A.
  4. Wiring Load:
    • Connect the electrical load (circuits to be powered) to the "Load Side" terminals of the ATS.
  5. Signal Indicator Connection (Optional): If desired, connect external signal indicator lights to the built-in standby opening signal output port for remote status monitoring. Refer to the wiring diagram on the device for specific terminal identification.
  6. Doğrulama: Double-check all wiring connections for tightness and correctness. Ensure no loose strands or exposed wires.

Warning: Incorrect wiring can lead to equipment damage, fire, or severe injury. Consult a professional electrician if you are unsure about any step.

6. Kullanım Talimatları

The RWRAPS ATS offers both automatic and manual operation modes.

6.1 Otomatik Mod

  1. Ensure the selector switch on the front of the ATS is set to the "Auto" position.
  2. Restore power to Source A (City Power). The ATS will automatically detect the presence of power and switch the load to Source A. The "A" indicator light will illuminate.
  3. If Source A power fails, the ATS will automatically detect the loss and, after a brief delay, switch the load to Source B (Generator Power), provided Source B is active. The "B" indicator light will illuminate.
  4. When Source A power is restored, the ATS will automatically switch the load back to Source A after a pre-set delay, ensuring priority for the main power source.

6.2 Manuel Mod

Manual operation is typically used for testing or in situations where automatic transfer is not desired.

  1. Set the selector switch on the front of the ATS to the "Manual" position.
  2. In manual mode, you can manually rotate the switch to select either "Source A" or "Source B" to power the load.
  3. Dikkat: When operating in manual mode, ensure that the selected power source is stable and capable of handling the load. Always return to "Auto" mode for normal operation.

Note: Manual operation must be in the "Man" position as indicated on some models (refer to Figure 3.2, 3.3, 3.4).

7. Bakım

The RWRAPS ATS is designed for minimal maintenance. However, periodic checks are recommended to ensure optimal performance and safety.

  • Görsel Muayene (Yıllık):
    • Fiziksel hasar, renk değişimi veya aşırı ısınma belirtileri olup olmadığını kontrol edin.
    • Check for loose connections or corrosion on terminals.
    • Ensure the DIN rail mounting is secure.
  • Temizlik:
    • Cihazınızı temiz ve toz ve kalıntılardan uzak tutun. Temizlik için kuru ve yumuşak bir bez kullanın.
    • Sıvı temizleyiciler veya çözücüler kullanmayın.
  • Functional Test (Periodically):
    • Bir güç kaynağını simüle edintage from Source A to verify automatic transfer to Source B.
    • Restore Source A power to confirm automatic transfer back.
    • Test manual operation by switching between Source A and Source B.

Warning: Always disconnect power before performing any maintenance that requires touching internal components.

8. Sorun Giderme

SorunOlası NedenÇözüm
No power to load in Auto mode.Both Source A and Source B are off, or one source is off and the other is not properly connected/active.Verify power supply to both Source A and Source B. Check circuit breakers and generator operation. Ensure ATS is in "Auto" mode.
ATS otomatik olarak geçiş yapmaz.Selector switch is in "Manual" position, or a power source is not detected.Set selector switch to "Auto". Check power input to both sources. Inspect wiring for loose connections.
Indicator light for active source is off.Faulty indicator light or no power to that source.Verify power to the corresponding source. If power is present, the indicator light may need replacement (contact support).
Cihaz çalışma sırasında ısınıyor.Overload, loose connections, or inadequate ventilation.Reduce load if exceeding rated current. Tighten all terminal connections. Ensure proper airflow around the device. If problem persists, disconnect power and contact support.

9. Garanti ve Destek

Garanti bilgileri veya teknik destek için lütfen doğrudan satıcınızla veya üreticiyle iletişime geçin. Satın alma belgesi olarak satın alma fişinizi saklayın.

Manufacturer: RWRAPS

Please refer to the product packaging or the seller's information for specific contact details and warranty terms.